MCCB vs MCB: Which Does Your Panel Board Need?
MCCB or MCB? How breaking capacity, the IEC 60898-1 and IEC 60947-2 standards, selectivity and temperature derating decide the right breaker for each board.
Read moreWhat to look for in a VSD for air handling units, cooling towers and chilled-water pumps: humidity and IP rating, harmonics, BMS protocols and cooling tower checks.
The best VFD for HVAC is not a brand. It is the drive whose environmental rating, harmonic performance, fan and pump functions and building management system (BMS) protocol match the plant it will serve. For a cooling tower fan, that means a variable-torque drive installed out of the weather or in an IP55 enclosure, with skip frequencies and catch-on-the-fly, a motor and cable checked for inverter duty, and speed controlled from condenser-water temperature. Yes, you can use a VFD on a cooling tower fan motor, provided you check the motor, cabling and tower mechanics first.
This guide covers specifying variable speed drives (VSDs, also called VFDs or inverters) for air handling units (AHUs), cooling towers and chilled- and condenser-water pumps in Singapore, using data for the ranges we supply and our own HVAC projects.

In this article
Fans and centrifugal pumps are variable-torque loads whose power falls roughly with the cube of speed. The IEA 4E Electric Motor Systems Platform reports that motor systems used 36% of electricity in buildings worldwide in 2023. NEA’s Motor Driven Systems reference manual shows a typical fan system reaching only about 40% overall efficiency once every component is counted. HVAC also brings humid plant rooms, rooftop towers, BMS integration and fire safety interfaces. The features we look for:
| Feature | Why it matters in HVAC | Examples from the ranges we supply |
|---|---|---|
| Normal-duty (variable-torque) rating | Fans and pumps are normal-duty loads, so the drive need not be oversized | Himel HAVSP normal-duty ratings; Himel X Series XP range for fan and pump applications |
| PID control with sleep | Holds a set point from a sensor and stops at low demand | HAVSP: adjustable PID regulator with sleep mode |
| Skip (jump) frequencies | Steps over resonant speeds | ATV212: machine protection via skip frequency function (resonance suppression) |
| Catch a spinning load | Restarts a windmilling fan without tripping | ATV212: catching a spinning load with speed detection |
| Fire mode or forced operation | Keeps a fan running in a fire where the design requires it | ATV212 forced operation with fault inhibition; HAVSP fire override mode |
| Harmonic mitigation | Limits distortion on the building supply | ATV212: THDi below 35% without chokes; X Series: built-in DC reactor, THDi can reach under 35% (check which ratings include the reactor) |
| BMS communication | Start, stop, speed, kWh and faults via the BMS | ATV212: Modbus, BACnet, Metasys N2, Apogee FLN P1 as standard; X Series: options including BACnet MS/TP and Modbus TCP; HAVSP: Modbus |
| Environmental robustness | Plant rooms are humid and sometimes dusty | ATV212: IP21 or IP55 versions; X Series: full coating PCB and dust shield cover |
The Meteorological Service Singapore gives a mean annual relative humidity of around 82%, with readings above 90% before sunrise. Drive datasheets assume non-condensing air:
| Drive | Enclosure | Humidity rating | Operating temperature |
|---|---|---|---|
| Himel HAVSP Smart Pump (37 kW example) | IP20 | 0–95% without condensation | −10 to 40 °C |
| Himel X Series | IP20, Type 1 | Up to 95% RH | −10 to 40 °C without derating; 40–50 °C with derating |
| Schneider ATV212 (H versions) | IP21 (IP41 on upper part) | IEC 60721-3-3 classes 3C1 and 3S2 | −10 to 50 °C without derating |
| Schneider ATV212 (W versions) | UL Type 12 / IP55 | IEC 60721-3-3 classes 3C1 and 3S2 | −10 to 40 °C without derating |
The Hydraulic Institute and Europump guide to variable speed pumping warns that drive electronics cope less well with damp and corrosive locations than conventional starters. In practice:
Yes. Our projects at Singapore EXPO, Seletar Mall and Silicon Box all include cooling tower drives. Check these before you specify:
A normal-duty, variable-torque drive with fan and pump software. A heavy-duty or closed-loop industrial drive adds cost without benefit. This matrix is a guide to fit, not a ranking:
| Application | Features that matter most | Ranges we supply that fit |
|---|---|---|
| Cooling tower fan | Normal duty, skip frequencies, catch spinning load, PID on condenser-water temperature, IP rating for location | Himel HAVSP, Himel X Series (XP), Schneider ATV212 |
| Chilled- and condenser-water pumps | PID on differential pressure or temperature, multi-pump cascade, sleep, harmonic performance | Himel HAVSP, Himel X Series, Schneider ATV212; Schneider ATV630 for larger or process duties |
| AHU supply and return fans | BMS protocol, PID on duct pressure or supply temperature, fire mode where required | Schneider ATV212, Himel X Series, Himel HAVSP |
| Carpark and smoke-purge ventilation fans | Fire override or forced operation, configuration to the fire engineer’s design | Himel HAVSP (used on our carpark ventilation projects) |
| Industrial process fans with precise speed or torque control | Closed-loop vector control, encoder feedback, heavy-duty rating | WEG ADV200, Himel HAVXS Expert Series |
The WEG ADV200 and Himel HAVXS Expert Series suit machinery needing precise speed or torque (see how the HAVXS minimises motor wear); for HVAC fans and pumps, the ranges in the first four rows fit better.
A drive’s diode rectifier draws current in pulses, adding harmonic distortion. IEEE 519 is commonly used to set limits, and specifications may add a per-drive THDi (total harmonic current distortion) limit. Two published approaches:
On our ST Aerospace Aviation Centre project at Seletar Aerospace Park, every chilled- and condenser-water drive had to stay below 35% THDi, and we measured each one during testing and commissioning. With a similar clause, ask for THDi at the actual rating and budget for measurement.
Settle network or hardwired control early, because options differ:
Retrofits need care. At Singapore Polytechnic (about 30 drives) and Republic Polytechnic (about 40 drives), the replacement HAVSP drives were configured to work with each campus’s existing controls and verified at commissioning. Get the existing points list, signal types and protocol before ordering.
Yes, where fans and pumps can run below full speed. US DOE Motor Systems Tip Sheet #11 notes that with no static lift, power varies with the cube of speed, so a 20% speed reduction can cut input power by about 50%.
| Fan speed | 100% | 90% | 80% | 70% | 60% | 50% |
|---|---|---|---|---|---|---|
| Shaft power (cube law) | 100% | 73% | 51% | 34% | 22% | 12.5% |
A 7.5 kW tower fan motor draws 6.5 kW at full speed for 4,000 hours a year. With a drive, it runs at 70% speed for 3,000 hours and full speed for 1,000. Using DOE’s typical 10 hp drive efficiencies (about 92% at this part load, 96% at full load):
If the fan currently cycles on and off, compare against its actual hours, and measure before and after. Our ATV212 HVAC energy article and VSD efficiency guide go further into the energy side.
We don’t rank brands: reliability depends more on application fit, installation and commissioning than on the logo. The Carbon Trust VSD technology guide lists the usual causes of drive problems: high ambient temperature, insufficient cooling, water or dust ingress, incorrect parameters and loose terminals.
The ranges we supply for AHUs:
At GIIS, we supplied HAVSP drives for the Phase 2 AHUs, configured to the operating accuracy needed to maintain cooling capacity for classrooms and laboratories, then tested and commissioned.
Checks drawn from our HVAC projects:
If a pump only ever runs at full speed, a soft starter may be the better tool. See our guide to soft starter vs VFD for pumps.
Send the motor nameplates, application, drive location and BMS protocol through our contact page and we will propose drives from our variable speed drive ranges, with datasheets. See also our HVAC and chilled-water solutions.
Yes. Check the motor’s insulation and age, keep the motor cable short or add a filter, set the minimum speed from the tower and gearbox makers’ data, programme skip frequencies around any resonance, and enable catch-spinning-load so a windmilling fan can restart.
A normal-duty, variable-torque drive with fan and pump functions: PID control from condenser-water temperature, skip frequencies, catch spinning load and a suitable IP rating for where it is installed. A heavy-duty industrial drive is not needed.
The best VFD for HVAC is the one that matches the plant: a normal-duty rating, HVAC functions such as PID, sleep and fire mode, the BMS protocol the building uses, acceptable harmonics and an enclosure suited to the location. We supply Himel and Schneider Electric drives designed for these duties.
Reliability depends mainly on correct rating, a dry and ventilated installation, correct parameters and good commissioning. We supply the Himel HAVSP and X Series and the Schneider ATV212 for air handling units, and we test and commission them on site.
Inside a ventilated or air-conditioned panel, an IP20 or IP21 drive is normal. Near a cooling tower or in a damp area, use an IP55 drive or a suitable enclosure, because morning humidity in Singapore regularly exceeds 90%.
Yes, when fans and pumps can run below full speed. Fan and pump power falls roughly with the cube of speed, so a 20% speed reduction can cut input power by about half. In our worked example, a 7.5 kW cooling tower fan saves about 12,000 kWh a year.
Send Jason the model or your motor rating — we'll confirm availability the same business day.