Technical Guides

Soft Starter vs VFD: Which Should Your Pump Use?

Soft starter or VFD for your pump? Compare starting current, running energy, harmonics and cost, with a decision matrix by pump duty, worked numbers and Singapore fire pump projects.

13 min read By the Trans-Digi Global team

Use a soft starter when the pump runs at one fixed duty and you only need a gentler start and stop. Use a variable frequency drive (VFD) when the flow or pressure the pump must deliver changes through the day, because only a drive can slow the pump down and cut running energy. A soft starter limits starting current to roughly 3 to 4 times motor current and then steps out of the circuit; a VFD keeps starting current within its own rating and controls speed continuously, at the cost of a higher price, around 3–4% losses at full speed and current harmonics that must be managed.

Below: how the two differ, a decision matrix by pump duty, worked energy numbers, how fire pumps fit in, and what we check on site, using manufacturer data and our own Singapore projects.

Singapore Rail Test Centre in Tuas, where a 132 kW Himel HASXS soft starter serves the fire pump system

Key takeaways

  • A soft starter manages only the start and stop, then bypasses itself.
  • A VFD (also called a VSD or inverter) controls speed for the whole run, which saves energy only when demand varies.
  • On a pump that always runs flat out, a VFD adds roughly 3–4% losses. In our worked example, that costs about S$800 a year on a 30 kW pump.
  • On variable-demand pumps the saving can be large, but static head shrinks it. Measure the duty first.
  • Both appear on Singapore fire pump systems, set up to SCDF Fire Code 2023 and the consultant’s design.

In this article

What is the difference between a soft starter and a VFD?

A soft starter is a solid-state motor starter covered by IEC 60947-4-2. It uses thyristors to raise the voltage to the motor gradually, limiting the current and torque during acceleration, then closes a bypass contactor so the motor runs directly from the supply. The Himel HASXS we supply is a typical example. Its 132 kW datasheet lists voltage-ramp starting, an integrated bypass, and start and stop times adjustable from 2–100 s and 1–50 s.

A VFD rectifies the incoming AC supply to DC and then rebuilds an AC output at whatever frequency and voltage the motor needs. Because motor speed follows frequency, the pump can run at any speed for as long as it runs. Pump drives such as the Himel HAVSP Smart Pump Series add pressure control and protection functions on top.

Soft starterVFD
Starting currentAbout 3–4 × rated current: 300% for a centrifugal pump on the ATS480, about 3.5 × on the RSGDWithin the drive’s rating: 75 A continuous, 90 A for 1 minute on the 37 kW HAVSP
Speed during runningFull speed only (motor on bypass)Variable. The HAVSP output range is 0–599 Hz
Losses at full speedLow once bypassed (Himel, HASES)About 3–4%: 96–97% typical drive efficiency at 75–100% load (US DOE)
Running energy savingNone. It does not change speedLarge on variable-flow pumps, small or negative on fixed-duty pumps
StoppingTorque-controlled soft stop to reduce water hammer (ATS480, RSGD)Controlled ramp-down to any speed, plus PID, sleep and multi-pump functions
Current harmonicsThe motor runs straight from the supply once bypassedDrawn continuously; check against the project limit
Sources: Schneider Electric ATS480 catalogue; Carlo Gavazzi RSGD brochure; Himel HASES catalogue; Himel HAVSP4T0370P datasheet; US DOE Motor Systems Tip Sheet #11.

The starting problem both devices solve is the direct-on-line (DOL) start. Schneider Electric’s guide to DOL starters puts the inrush of a motor switched straight onto the supply at typically 6 to 8 times its rated running current. Carlo Gavazzi’s RSGD brochure adds that newer high-efficiency motors can draw more: about 10 × for IE3 and up to 15 × for IE4 motors.

Should I use a soft starter or variable frequency drive for my pump?

Decide from the pump’s duty, not the price list. The Hydraulic Institute and Europump guide to variable speed pumping recommends starting with a duration diagram: how many hours a year the system needs each flow rate. Then work through these steps:

  1. Map the duty. Log flow, pressure, running hours and starts for a typical week, or take them from the BMS.
  2. Find the static head, the height and fixed pressure the pump must overcome even at zero flow. The Hydraulic Institute warns that in systems with high static head, “a small turn down in speed greatly reduces flow rate and pump efficiency”, and that applying the affinity laws there “can also lead to major errors”.
  3. Check the supply. Both devices remove the 6–8 × DOL inrush, so a weak supply alone is no reason to buy a drive.
  4. Decide how the pump must stop. The US DOE sourcebook Improving Pumping System Performance notes that rapid acceleration of large volumes of fluid can create damaging water hammer. Both devices can ramp down under control.
  5. List the control functions. Constant-pressure PID, cascading, sleep and dry-run protection are drive functions; a float or pressure switch start suits a soft starter.
  6. Check harmonics, heat and environment. The Hydraulic Institute notes that drive electronics cope less well with corrosive and damp locations than conventional starters.
  7. Check the regulations for fire pumps (see below).

A fixed duty or high static head points to a soft starter. Varying demand on a friction-dominated system, such as a chilled-water loop, points to a drive, whose capital cost the Hydraulic Institute notes can often be offset by removing control valves, bypass lines and conventional starters.

When to use a soft starter vs a VFD: decision matrix

Applied to common pump duties in Singapore buildings and plants (a starting point, not a substitute for the consultant’s calculations):

Pump dutyTypical demand profileUsual choiceWhy
Fire pump (wet riser, sprinkler, hose reel)Starts on demand, then runs at full dutySoft starter, or a drive with fire override where the design calls for itThe job is a reliable start and full output. Protection settings must follow Fire Code clause 5.2.3
Transfer pump filling a roof tankFixed flow, high static head, on/off by levelSoft starterLittle to save by slowing down; a soft stop limits water hammer in the riser
Domestic water booster setDemand varies hour by hourVFD (pump drive with PID and sleep)Holds set pressure and avoids running at full speed at low demand
Chilled-water secondary pump, variable flowLoad follows cooling demandVFDFriction-dominated loop, so speed reduction gives large savings
Constant-flow chilled- or condenser-water pumpFixed flow while the chiller runsSoft starter (or a drive used for balancing)A soft starter tames the start on large motors; a drive saves energy only if the flow can drop
Sump or sewage ejector pumpFrequent level-switched startsSoft starter sized for the starts per hourFixed duty; check the starter’s starts-per-hour rating
Guidance compiled from the Hydraulic Institute/Europump guide, US DOE Tip Sheet #11 and the Carbon Trust VSD technology guide. Confirm against the project design.

The Carbon Trust’s VSD technology guide agrees: where demand already matches the motor’s full-load capacity, a VSD “would only add to the overall system losses”.

Variable speed drive vs soft starter: the energy maths

Take a 37 kW centrifugal pump motor on 400 V, drawing 30 kW at its duty point, priced at the SP Group regulated tariff of 28.59 cents/kWh before GST (October–December 2026). Your contracted rate may differ.

Example 1: fixed-duty transfer pump, 3,000 hours a year

On bypass, the soft starter adds almost nothing. A VFD at 50 Hz adds its own losses: US DOE Motor Systems Tip Sheet #11 gives 97% typical efficiency at full load for a 50 hp drive, so 30 kW ÷ 0.97 = 30.9 kW. The extra 0.9 kW over 3,000 hours is about 2,800 kWh, roughly S$800 a year more, before the higher purchase price.

Example 2: variable-demand circulating pump, 6,000 hours a year

Now the same pump serves a friction-dominated loop that could run at 80% speed. Power varies with the cube of speed (0.8³ = 0.51). Allowing 95% drive efficiency at part load (DOE table): 30 kW × 0.51 ÷ 0.95 ≈ 16.2 kW, about 13.8 kW less than full speed, or roughly 83,000 kWh and S$23,700 a year.

Treat that as a ceiling: a throttled pump does not draw full power at reduced flow, and static head cuts the saving. Our article on how the Schneider ATV630 cuts pump and fan energy covers the measurement.

Starting current on the same motor

Full-load current is about 67 A (assuming 0.86 power factor and 93% efficiency; check the nameplate):

Starting methodPeak starting currentBasis
Direct-on-lineAbout 400–535 A6–8 × rated current (Schneider Electric)
Soft starterAbout 200 A300% current limit typical for a centrifugal pump (ATS480 catalogue), 5–15 s start
VFD (37 kW HAVSP)75 A continuous, up to 90 A for 1 minuteHimel HAVSP4T0370P datasheet, normal duty
Calculated figures for illustration. Starting current with a soft starter depends on the current limit set at commissioning.

Fire pumps: what our LTA projects used

A fire pump’s duty is simple, but a failed start is serious. SCDF’s Fire Code 2023, clause 5.2.3 sets rules for these motor circuits. Cable connections must be protected by HRC fuses or MCCBs with magnetic release, able to carry the motor’s stalled current for at least 75% of the time that would damage the windings. Any no-volt release must reset automatically, and thermal overload trips are not permitted. Clause 6.8 requires the fire pumping system to keep performing when a pump or its control system is out of service.

Our fire pump references show both approaches:

Neither device is right for every fire pump; the settings must follow the Fire Code and the design. On chilled-water plant, our Gateway East project used more than 10 HASXS units (37–55 kW) as standby starters for motors in service for over 10 years.

Harmonics, cables and panel space

A drive’s rectifier draws current in pulses, adding harmonic distortion. IEEE 519 is commonly used to set limits, and specifications may add their own: on our ST Aerospace project, each drive had to stay below 35% THDi (total harmonic current distortion), and we measured every one.

US DOE Motor Systems Tip Sheet #15 adds that cable runs of 50 feet (about 15 m) or more from a PWM drive almost always need mitigation, such as a load reactor or dV/dt filter, and the Hydraulic Institute recommends insulated non-drive-end bearings above 100 kW.

Both need a proper enclosure: the HASXS is IP00 and the HAVSP IP20, each rated for non-condensing humidity only.

Common mistakes and what we check on site

  • A drive on a pump that never slows down: 3–4% losses for no saving.
  • Affinity-law savings quoted for high static head pumps.
  • Soft starter current limit set too low, so the pump never reaches speed. Schneider’s typical centrifugal pump figures are 300% and 5–15 s.
  • Ignoring starts per hour. Carlo Gavazzi notes soft starters are typically designed for 10–20 starts per hour; more may need oversizing.
  • Thermal overload trips on fire pump circuits, which clause 5.2.3 does not permit.
  • Removing a throttling valve without replacing its shut-off role. The Carbon Trust notes a VSD pump cannot act as a shut-off or back-flow device at zero flow.
  • Long motor cables with no output filter on retrofits.

Soft starters and drives we supply for pumps

We supply, test and commission both:

For product-level detail, see our guides to the Schneider ATS480 soft starter, the Schneider ATS22, Carlo Gavazzi soft starters, the Himel Smart Pump Series and how VSDs improve motor efficiency. For a recommendation, send the pump duty and motor nameplate through our contact page.

Frequently asked questions about soft starters vs VFDs

What is the difference between a soft starter and a VFD?

A soft starter ramps the voltage up to start the motor smoothly, then bypasses itself so the motor runs at full speed. A VFD controls the motor’s frequency and voltage for the whole run, so it can change the speed. Only a VFD can save running energy.

Should I use a soft starter or variable frequency drive for my pump?

Use a soft starter if the pump runs at one fixed duty, such as a transfer or fire pump, and you only need to reduce starting current and water hammer. Use a VFD if the flow or pressure demand varies, such as on a booster set or a variable-flow chilled-water loop.

When should I use a soft starter instead of a VFD?

Choose a soft starter when the motor must run at full speed whenever it runs, when the budget or panel space is tight, or when you want to avoid adding drive harmonics. On a fixed-duty pump, a VFD adds roughly 3–4% losses and saves nothing.

Does a variable speed drive save more energy than a soft starter?

Only when the pump can run slower. On centrifugal pumps, power falls with the cube of speed, so running at 80% speed needs about half the power. At full speed, a soft starter on bypass is slightly more efficient than a drive.

Can a VFD replace an existing soft starter on a pump?

Yes, if the duty varies enough to justify it. Check the motor insulation and cable length, add a pressure or flow sensor for control, plan for harmonics and heat in the panel, and keep a check valve or other shut-off function at the pump discharge.

Are soft starters used on fire pumps in Singapore?

Yes. We have supplied 132 kW and 160 kW Himel HASXS soft starters for LTA fire pump systems. Drives with fire override settings are also used on fire pump systems. Either way, the settings must follow SCDF Fire Code 2023 and the consultant’s design.

Sources

Have a project in mind?

Send us your motor rating, voltage, application and quantity. We'll get back to you fast.