Read moreThe Himel VSD Smart Pump Series (HAVSP) reduces energy waste in pump systems by running each pump only as fast as the system needs, holding pressure or flow with built-in PID control instead of throttling valves or bypass lines. Because pump power falls roughly with the cube of speed, a 20% speed reduction can cut […]
The Himel VSD Smart Pump Series (HAVSP) reduces energy waste in pump systems by running each pump only as fast as the system needs, holding pressure or flow with built-in PID control instead of throttling valves or bypass lines. Because pump power falls roughly with the cube of speed, a 20% speed reduction can cut input power by about half, and pump-specific functions such as multi-pump staging, sleep mode and dry-run protection keep that saving without risking the equipment.
In this article
This article explains where energy is lost in a typical pump system, how the HAVSP addresses each loss, and what we have learned supplying, testing and commissioning these drives on Singapore projects, from HDB fire pump systems to chilled-water plants at Singapore EXPO and Tanah Merah Ferry Terminal.
Pumps are among the biggest motor loads in any building or plant. The Hydraulic Institute and Europump guide Variable Speed Pumping, published with the US Department of Energy, notes that pumping systems account for nearly 20% of the world’s electric motor energy and 25% to 50% of electrical energy use in certain industrial facilities. The waste tends to come from the same few places:
Singapore’s NEA Motor Driven Systems reference manual works through a typical pumping system with a drive at 95% efficiency, a motor at 88%, a coupling at 98% and a pump at 60%, giving an overall system efficiency of only about 49%. In a worked example in the same manual, opening a throttled valve and replacing a poorly matched pump moved system efficiency from about 50% to about 70%, which the manual equates to energy savings of about 50%. The lesson is that the pump, the controls and the operating point matter as much as the motor nameplate.
The affinity laws describe a centrifugal pump at different speeds: flow is proportional to speed, head to the square of speed, and power to the cube of speed. The US Department of Energy’s Adjustable Speed Drive tip sheet gives the practical version: reducing speed by 20% can reduce input power requirements by approximately 50%.
| Control method | How flow is reduced | Energy outcome |
|---|---|---|
| Throttling valve | Pump runs at full speed against a partly closed valve | Little saving; excess head is dissipated across the valve |
| Bypass line | Surplus flow recirculated to suction | Little or no saving; pump still delivers full flow |
| On/off cycling | Pump runs at full speed in bursts | Saves run-hours but causes full-current starts and pressure swings |
| Variable speed drive | Motor speed reduced to match demand | Largest saving on friction-dominated systems; 30–50% reported in many installations |
Static head limits the benefit. In a system that must lift water a fixed height, part of the pump’s head is needed regardless of flow, so the speed cannot fall as far as the cube law suggests. The Variable Speed Pumping guide points out that the ratio of static to friction head over the operating range decides how much a VSD can save, and the DOE tip sheet notes that drives do not save energy where equipment runs close to full load most of the time. Closed chilled-water and condenser-water loops, which are mostly friction head, are usually strong candidates. Tall-building transfer pumps lifting to a roof tank may save less.
The HAVSP is designed around pumping duties rather than adapted to them. Himel’s datasheet for the 15 kW model (HAVSP4T0150P) lists these built-in functions:
| HAVSP function | What it does | Why it matters |
|---|---|---|
| Adjustable PID regulator with sleep mode | Holds pressure or flow at a set point and idles the pump at low demand | Avoids running a pump to hold pressure when nothing is being drawn |
| Multi-pump control | Stages duty and assist pumps as demand changes | Runs fewer pumps nearer their best efficiency point |
| Dry-run protection | Stops the pump if it loses water | Protects seals and impellers |
| Energy and flow calculator | Estimates energy and flow from drive data | Gives facility teams a baseline for measuring savings |
| Pump cleaning | Runs a pump-cleaning routine | Useful on sump and wastewater duties |
| Frost and condensation protection | Guards against frost and condensation conditions | Relevant to humid plant rooms |
| Fire override mode | Maintains operation during critical conditions, for example higher-speed fan operation for smoke purging | Supports fire pumps and smoke-control fans |
The same datasheet lists a 380–480 V three-phase supply, V/F and sensorless vector control, normal-duty overload of 38.4 A for one minute on a 32 A continuous rating (120%), output frequency up to 599 Hz, a Class C3 EMC filter, Modbus communication, IP20 protection and an operating ambient of −10 °C to 40 °C. The product page lists ratings up to 315 kW, along with pipe-burst and overpressure protection.
HAVSP drives feature in most of our published project references, which show where pump-specific features earn their place.
At Singapore EXPO, we supplied, tested and commissioned 7.5 kW and 37 kW HAVSP drives for cooling towers, chilled-water and condenser-water pumps. A key requirement was reliable starting and operation of motors that had been in service for more than ten years, so the existing motors were retained. The replacement arrangement also helped optimise cabling and installation cost.
At Tanah Merah Ferry Terminal, the client wanted a more cost-effective replacement for its chilled-water and condenser-water pump drives that would also reduce ongoing maintenance requirements. The HAVSP’s compact footprint simplified fitting into the existing installation space, and the layout reduced cable requirements. At Seletar Mall, 33 HAVSP drives from 0.75 kW to 15 kW now serve cooling towers, chilled-water pumps, condenser-water pumps and basement carpark fans under one drive platform.
Our largest single programme was more than 100 HAVSP drives for fire pump systems across HDB estates under four Town Councils: Holland-Bukit Panjang, Tanjong Pagar, West Coast (now West Coast–Jurong West) and Jalan Besar. Each installation needed the correct VSD parameter settings for the fire pump application, followed by testing and commissioning.
Fire pumping is governed by SCDF’s Fire Code. Clause 6.8 of Fire Code 2023 requires pumping systems for wet rising mains, hose reels, sprinklers and hydrants to have redundancy, so system performance is not affected when one pump or its control system is out of service. Drive configuration on these systems is therefore about dependable operation first and energy second.
At the Silicon Box semiconductor plant, the HAVSP drives for chilled-water, condenser-water, cooling tower and carpark exhaust systems had to meet energy-performance requirements set by the project’s energy consultants. At the ST Aerospace aviation centre, the chilled-water and condenser-water drives had to stay below 35% THDi, and we measured and monitored the harmonic level of every installed drive before handover. Harmonic limits like this are usually written with reference to IEEE 519.
Our Tengah Plantation C1 reference records that the HAVSP series is approved for use in HDB projects and is certified under the Singapore Green Building Product (SGBP) scheme. SGBC’s scheme uses a 1-to-4-tick rating, and certified products can earn points towards a building’s BCA Green Mark rating.
Manufacturing companies looking at efficiency upgrades may also want to check NEA’s Energy Efficiency Fund (E2F), which co-funds investments in energy-efficient technologies for eligible companies with group annual sales turnover of up to S$500 million. Eligibility and qualifying equipment are set by NEA, so confirm directly before planning around a grant.
Trans-Digi Global is an authorised partner for Himel and holds local stock of the Smart Pump Series. Our services include product selection and sizing, installation and panel integration, and testing and commissioning, including PID and set-point configuration, pump cascade, alternation and sleep/wake set-up, and BMS interface verification, with commissioning records at handover.
If your project needs process-level functions beyond pumping, compare the HAVSP with the Himel X Series; our guide to understanding the Himel VSD X Series covers it in detail. For the wider picture, read how variable speed drives improve motor efficiency.
Related reading: VFD sizing for pumps: a step-by-step guide, and how to replace a failed VFD on site, with a commissioning checklist.
It is Himel’s HAVSP range of three-phase variable speed drives built for pumping, with PID control, sleep mode, multi-pump control, dry-run protection and fire override mode built in.
Pump power falls roughly with the cube of speed, so a 20% speed reduction can cut input power by about half. Industry guidance reports 30–50% savings in many pump installations, with less on systems dominated by static head.
Yes. We have supplied more than 100 HAVSP drives for fire pump systems across HDB estates, with fire-pump-specific parameter settings and testing and commissioning. The design must follow SCDF’s Fire Code and the consultant’s specification.
Often, yes. At Singapore EXPO, HAVSP drives were commissioned to run motors that had been in service for more than ten years. Check the motor’s condition and insulation before retrofitting.
Our Tengah Plantation C1 reference records the HAVSP series as approved for use in HDB projects and SGBP-certified, which can contribute points towards BCA Green Mark.