Choosing a VSD for Commercial HVAC and Cooling Towers
What to look for in a VSD for air handling units, cooling towers and chilled-water pumps: humidity and IP rating, harmonics, BMS protocols and cooling tower…
Read moreFixed-speed motors quietly waste power every day. How the Altivar Process ATV630 matches speed to real demand — and why the affinity laws put pump and fan savings at a typical 20–50%.
9 June 2026 · 13 min read · Trans-Digi Global
The short answer: a centrifugal pump or fan’s power draw falls roughly with the cube of its speed, so a drive that runs it 20% slower can cut its input power by close to half. The Schneider Altivar Process ATV630 variable speed drive does this by matching motor speed to the real flow or pressure demand instead of running flat out and throttling. On variable-duty pumps and fans, savings in the 20–50% range are well documented: the UK Carbon Trust puts a 20% speed reduction at up to 50% less energy, and Hydraulic Institute, Europump and US Department of Energy guidance reports 30–50% savings in many pump installations. The exact figure on your site depends on the load profile and how much static head the system has, and this guide shows how to estimate it before you buy.
In this article
Pumps are a large share of motor energy use. Guidance from the Hydraulic Institute, Europump and the US DOE states that pumping systems account for nearly 20% of the world’s energy used by electric motors. In a Singapore building, most of that load sits in chilled-water pumps, condenser-water pumps, cooling-tower fans, air-handling units and carpark ventilation fans. Those are the duties this article covers.
Centrifugal pumps and fans are variable-torque loads. Their behaviour with speed is described by the affinity laws:
That cube relationship is where the savings come from. A fixed-speed pump controlled by a throttling valve, or a fan controlled by a damper, keeps the motor at full speed and burns off the surplus energy across the valve or damper. A VSD such as the ATV630 removes the surplus at source by lowering the speed. The DOE pumping sourcebook calls pump speed adjustment “the most efficient means of controlling pump flow”, and notes that most of the savings come from cutting friction, throttling and bypass losses.
The table below applies the ideal affinity laws to a pump drawing 15 kW at full speed. It is an illustration, not a site measurement: it assumes a friction-dominated system with no static head and ignores the small losses in the drive and motor.
| Speed | Flow | Head | Power (% of full) | Power for a 15 kW pump | Saving vs full speed |
|---|---|---|---|---|---|
| 100% | 100% | 100% | 100% | 15.0 kW | – |
| 90% | 90% | 81% | 72.9% | 10.9 kW | 27% |
| 80% | 80% | 64% | 51.2% | 7.7 kW | 49% |
| 70% | 70% | 49% | 34.3% | 5.1 kW | 66% |
| 60% | 60% | 36% | 21.6% | 3.2 kW | 78% |
| 50% | 50% | 25% | 12.5% | 1.9 kW | 88% |
Few plants run at one speed all day, so a duty profile gives a more realistic view. Suppose the same pump spends 30% of its hours at full speed, 40% at 80% speed and 30% at 60% speed. Its average power is (0.3 × 100%) + (0.4 × 51.2%) + (0.3 × 21.6%) ≈ 57% of full-speed power, a saving of about 43% compared with running at full speed all the time. That is why 20–50% is a sensible planning range for variable-duty pumps and fans. A system that seldom slows down will sit at the bottom of the range or below it. A system that spends long hours at low demand can do better.
Every reputable source attaches conditions to these numbers, and you should check them before signing off a business case:
The short answer: usually less than on a circulating pump, but still worthwhile where demand varies through the day. A domestic water booster set has to hold a fixed delivery pressure at the top of its zone, so much of its head is static head that does not fall when the pump slows down. Treat the 20–50% range above as an upper bound for a booster, not a forecast. The Hydraulic Institute and Europump guide Variable Speed Pumping warns that using the affinity laws to calculate savings in systems with static head “can also lead to major errors”, so the figure for your building has to come from the system curve and a measured demand profile.
A booster set (also called a pressure booster set) is a packaged group of pumps, a controller and a pressure vessel that raises mains or tank water to the pressure each floor needs. In high-rise buildings, the CIBSE Journal guide to pumping wholesome water notes that supply is typically zoned, with a separate pump set and riser for each pressure zone. Where a drive does save energy on a booster, the saving comes from these sources:
| Where the saving comes from | How the drive achieves it |
|---|---|
| No over-pressure at low demand | Holds the set pressure by PID control from a pressure transmitter, instead of letting pressure rise when demand is below design. CIBSE describes this as preventing “high-pressure overrun”. |
| Each pump nearer its best efficiency | Cascades duty and assist pumps as demand changes. CIBSE notes the controller can minimise energy use “by operating each pump closer to its peak efficiency”, with pumps selected for speeds of typically 25% to 100%. |
| Lower pressure at low flow | The ATV630 friction loss compensation lowers the pressure set point at low flow. |
| No running at zero demand | Sleep/wake-up stops the pump instead of idling against a closed system. |
| Removing oversizing | An estimated 75% of pump systems are oversized, many by more than 20%. A drive lets the set run at the speed the building actually needs. |
Variable speed sets also bring benefits beyond the kWh figure. CIBSE notes that soft start and stop reduce hydraulic and electrical stresses, and that expansion vessels fitted to sets with variable speed drives are typically smaller.
Booster, transfer and pressurisation pumps are one of the pump and water system applications we support, with closed-loop pressure control, multi-pump cascade and alternation, sleep and wake operation and dry-run protection. Our published case studies do not report a measured booster-pump saving, so we do not quote one here. For pump-specific drives, see the Himel Smart Pump Series.
The ATV630 belongs to Schneider Electric’s Altivar Process ATV600 family, which Schneider describes as drives “focused on fluid management and processing and energy saving”. The points below come from Schneider’s ATV600 catalogue and programming manual.
For the connectivity and protection side of the drive, see our companion article on ATV630 smart motor control. For lighter HVAC duties, read about energy optimisation with the ATV212 HVAC drive.
Before requesting an ATV630 quotation, have these points ready. They decide whether the energy case holds and which reference to order:
Our published project references cover the same duties the ATV630 is built for. Most of them use Himel HAVSP Smart Pump Series drives rather than the ATV630, but they show what decides a successful pump or fan VSD project in Singapore buildings:
None of these published case studies reports a measured kWh saving, so we do not quote one here. Savings depend on the site, which is why the baseline and post-commissioning measurement steps above matter. See all our project success stories.
In Singapore, manufacturing companies may also be able to get co-funding through NEA’s Energy Efficiency Fund (E2F). In 2023, NEA raised support for pre-approved energy-efficient technologies to 70%. Check current eligibility and the list of supported technologies directly with NEA before planning a project around a grant.
Related reading: VFD sizing for pumps: a step-by-step guide.
On variable-duty centrifugal pumps and fans, 20–50% is a realistic planning range. A 20% speed reduction can cut input power by close to half, according to the affinity laws and Carbon Trust guidance. The actual saving depends on the load profile and how much static head the system has.
On pumps and fans whose demand varies, especially where flow is currently controlled by throttling valves, bypass lines or dampers. Slowing the motor removes that wasted energy at source.
Static head is fixed pressure the pump must overcome before any flow starts. In those systems, flow does not fall in proportion to speed, so the ideal cube-law saving is not reached. Industry guidance warns that applying the affinity laws directly to such systems can lead to major errors.
Yes. The drive holds a constant delivery pressure by PID control from a pressure transmitter, stages the duty and assist pumps as demand changes, and stops the pumps when there is no demand. The ATV630 includes booster control with multi-pump staging and sleep/wake-up. Because a booster works against a large static head, expect smaller savings than on a circulating pump, and estimate them from the system curve.
By slowing the pump to the flow or pressure actually needed, instead of throttling, bypassing or cycling it. A centrifugal pump’s power falls roughly with the cube of its speed, so a 20% speed reduction can nearly halve its input power, and the Hydraulic Institute and Europump guide reports savings of 30–50% in many rotodynamic pump installations. A drive also corrects oversizing, which the same guide estimates affects 75% of pump systems, and slower running reduces bearing and seal wear.
Yes. It has embedded Modbus TCP and Modbus serial communication, and option modules add BACnet MS/TP, EtherNet/IP, PROFINET, CANopen, PROFIBUS DP V1 and DeviceNet.
Record the motor’s energy use before the change, then use the ATV630’s built-in power measurement and kWh counters, which Schneider states are accurate to within 5%, to compare a similar period afterwards. Its Energy Saving screen can also compare consumption with the original system.
Trans-Digi Global supplies the Schneider Altivar Process ATV630 and the wider Schneider Electric range in Singapore, alongside our other variable speed drives. We also provide testing, commissioning and replacement services for pump and HVAC applications. Send us the motor rating, voltage, phase, quantity and application through our contact page. We will confirm the exact model, check stock and send a quotation the same business day.
Figures are taken from the publications listed. Drive ratings and functions vary by reference and firmware, so confirm them against the current Schneider Electric documentation for your exact part number.
Send Jason the model or your motor rating — we'll confirm availability the same business day.