
Choosing a VFD for Air Handling Units in HVAC Systems
How to choose the best VFD for an air handling unit: a checklist for fan duty, current, BACnet or Modbus, PID, EMC, IP rating, fire mode…
Read moreMotor starter panel components traced along a DOL power path: breaker, RCCB, AC-3 contactor, overload relay trip class and the start and stop circuit.
A direct-on-line motor starter panel has five working parts on the power path and control side. A breaker isolates and clears short circuits, and an RCCB adds earth leakage protection where the design calls for it. A contactor rated AC-3 switches the motor, and a thermal overload relay set to the motor’s full-load current guards the windings. Start and stop buttons, an auxiliary holding contact and pilot lights complete the control circuit.
This guide follows the current from the incoming terminals to the motor. Each stop names the component, its job and the one rating that matters most. Where we already have a detailed product guide, we link to it instead of repeating it.

Table 1 is the parts list in power-path order. Use it as a checklist when you build or review a panel schedule.
| Component | Job in the panel | Key selection point | Himel example |
|---|---|---|---|
| MCCB or MCB | Isolates the circuit and clears short circuits | Breaking capacity at least equal to the fault level at the panel | HDM3 MCCB, HDB9 MCB |
| Motor circuit breaker | Isolation, overload and short-circuit protection in one device | Thermal setting range covers the motor full-load current | HDP6 |
| RCCB | Trips on earth leakage current | Sensitivity, poles, voltage and earth-leakage class | HDB3VR |
| Contactor | Starts and stops the motor on command | AC-3 rated current and kW at the supply voltage | HDC3 |
| Thermal overload relay | Trips the contactor on sustained overload or phase failure | Setting range around the motor full-load current, plus trip class | HDR3S |
| Auxiliary contact block | Adds holding and signalling contacts | Contact composition and compatibility with the contactor | HF411 |
| Push buttons and pilot lights | Operator start, stop and status indication | Control voltage matches the contactor coil | Specified by the panel designer |

The first device on the power path is the breaker. It lets you isolate the starter and clears short-circuit current that the contactor cannot interrupt. Its breaking capacity must cover the prospective fault current at that point in the installation.
For a larger motor feeder, a Himel MCCB from the HDM3 range is the usual choice. Our guide on how to size a Himel MCCB walks through frame, breaking class and trip unit. Small motors on a final circuit may use a Himel MCB instead. Trans-Digi Global lists HDB9 data sheets with 10 kA breaking capacity and C-curve models from 6 A to 63 A. See choosing a Himel MCB for curve and pole choice, and our MCCB vs MCB guide for where the line falls.
A third option combines several jobs. The Himel HDP6 motor circuit breaker provides isolation, overload and short-circuit protection in a single device, with phase-loss protection.
A residual current circuit breaker, or RCCB, compares the current going out with the current coming back. If some current leaks to earth, it trips. It does not replace the breaker. Trans-Digi Global’s product page notes that RCCBs do not give complete overload or short-circuit protection on their own.
Schneider Electric’s sensitivity guide gives two reference levels. A 30 mA device is chosen for protection from electric shock by direct contact. A 300 mA device is chosen for protection from fire caused by leakage current.
| Sensitivity | Purpose stated by Schneider Electric | Himel HDB3VR availability |
|---|---|---|
| 30 mA | Protection from electric shock by direct contact | Available |
| 300 mA | Protection from fire due to current leakage | Available |
The Himel HDB3VR RCCB comes in two-pole and four-pole models from 10 A to 100 A. The data sheets list 10, 30, 100 and 300 mA sensitivities. The Himel HDB3VR425TC data sheet shows a four-pole, 25 A, 300 mA model rated 400 V AC, to EN/IEC 61008-1. It is Class AC, for AC. The two-pole HDB3VR225TA data sheet shows a Class A model for AC and DC.
Where does an RCCB circuit breaker sit in a starter panel? It sits after the breaker on the circuits the design engineer specifies, often socket outlets or exposed equipment. Whether a fixed motor circuit needs one, and at what sensitivity, is a design decision under SS 638. If a drive sits downstream, check the drive manual before choosing the RCCB class. WEG’s ADV200 guide, for example, calls for a type B device.
The contactor is the switch the operator commands. Its coil pulls in the main poles to start the motor and releases them to stop it. It gives no overload or short-circuit protection on its own.
Contactors are rated by utilisation category. Schneider Electric defines AC-3 as the category for squirrel cage motors, with breaking during normal running. On closing, the contactor makes an inrush of about 5 to 7 times the motor’s rated full-load current. On opening, it breaks the full-load current. Schneider Electric lists pumps, compressors, conveyors and air conditioning units as AC-3 duty. AC-1 covers loads with a power factor of at least 0.95, such as heaters.
Size the contactor by its AC-3 figure at your supply voltage, not its AC-1 figure. The Himel HDC3-1811 data sheet, for example, gives 18 A and 7.5 kW at 380 or 400 V in AC-3. The same data sheet lists a 220 or 230 V AC coil and one normally open plus one normally closed auxiliary contact. Our HDC3 contactor guide covers the full range and AC-4 duty.
The overload relay sits between the contactor and the motor. It does not break the motor current itself. When it trips, it opens a normally closed contact in the coil circuit, and the contactor drops out.
The Himel HDR3S2510 data sheet shows a 7 to 10 A adjustment range on the 25 A frame. It lists overload and phase failure protection, manual and automatic reset, a test button, a stop button and a trip indicator.
Setting the dial. Schneider Electric states that the overload dial represents the motor’s nominal current, or full-load amps. Read the full-load current from the motor nameplate and set the dial to it. As a general rule, pick a relay whose range places that value near the middle. A motor with a 9 A nameplate fits the 7 to 10 A HDR3S2510.
Choosing the trip class. Schneider Electric notes that IEC 60947-4-1 defines several overload relay classes, each with its own tripping curve. The class number is the longest trip time, in seconds, at six times the set current. A class 10 relay trips within 10 seconds, and a class 20 within 20 seconds.
| Trip class | Typical use according to Schneider Electric |
|---|---|
| 10A and 10 | Normal-duty motors |
| 20 | Heavy-duty motors with longer starts |
| 30 | Very long motor starting |
If a fan or loaded conveyor takes a long time to reach speed, a class 10 relay may trip during the start. Check the motor’s run-up time against the relay curve, and confirm the class on the relay data sheet. Our HDR3S overload relay guide covers ranges and common setting mistakes. Good contactor and overload relay selection starts from the same nameplate figure for both parts.
Tip: Never raise the dial above the nameplate current to stop nuisance trips. Find the cause first, such as a voltage drop, a jammed load or a lost phase.
Motor control panel wiring on a DOL starter usually follows three-wire control. In the general layout, a momentary start button energises the contactor coil. The contactor then holds itself in through one of its own normally open contacts. The stop button is normally closed and sits in series, so pressing it drops the contactor out.
This layout has a safety benefit. Schneider Electric explains that the latching contactor drops out after a supply or control interruption. It stays out until a new start signal. Two-wire control, using a maintained switch, restarts the machine when power returns.
The overload relay’s contact on terminals 95 and 96 sits in the coil circuit, as Schneider Electric’s DOL wiring note shows. A trip then drops the coil exactly as a stop would. The same note prefers 415 V AC control because it needs no neutral fed to the starter. Whatever voltage you choose, match it to the contactor coil.
Pilot lights show the operator what is happening. As a general layout, a run lamp can use a spare normally open contact on the contactor. A trip lamp needs a signalling contact on the overload relay, so check its data sheet. If you run out of contacts, the Himel HF411 block adds one normally open and one normally closed contact. Its data sheet lists compatibility with HDC3 contactors from 6 to 95 A and 120 to 630 A.
Safety note: All panel assembly, wiring, testing and setting must be done by a qualified, licensed electrical worker. Follow the manufacturer’s manual for every device and isolate the supply before work.
A DOL starter suits many pumps and fans. Its limit is the start itself. Schneider Electric puts the inrush at about 5 to 7 times full-load current.
Step up to a soft starter when the supply, the coupling or the pipework cannot accept that sudden start. Our article on what a soft starter does explains how it ramps the motor up. Step up to a variable speed drive when the process needs speed control during running, not only a gentler start. Our comparison of soft starter vs VFD sets out the choice by duty. If you fit a drive, the VSD start-up procedure covers commissioning.
Either way, the breaker and earth leakage stops on the map stay in place. The soft starter or drive replaces only the direct switching stage.
Motor starter panel components work as a chain. The breaker clears faults, the RCCB guards against leakage, the contactor switches and the overload relay protects the windings. Start from the motor nameplate and the fault level at the panel, and every other choice follows. Trans-Digi Global provides selection and sizing support for project applications. We supply Himel, Schneider Electric, WEG and Carlo Gavazzi products. Send us your motor list and we will check each component against the data sheets.
You need a breaker for isolation and short-circuit protection, a contactor rated AC-3, and a thermal overload relay set to the motor full-load current. Add start and stop buttons, an auxiliary holding contact and pilot lights for control. An RCCB is added where the design calls for earth leakage protection. A motor circuit breaker can replace the separate breaker and overload relay.
Start with the motor nameplate full-load current and supply voltage. Choose a contactor whose AC-3 rated current and kW at that voltage meet or exceed the motor. Then choose an overload relay whose adjustment range includes the full-load current, ideally near the middle. Check the trip class against the motor’s run-up time and confirm the pairing on the data sheets.
AC-3 is the utilisation category for squirrel cage motors that are switched off during normal running. Schneider Electric explains that the contactor makes an inrush of about 5 to 7 times full-load current and breaks the full-load current. Always size a motor contactor by its AC-3 figure. The AC-1 figure is higher but applies to resistive loads such as heaters.
Schneider Electric gives 30 mA for protection from electric shock by direct contact and 300 mA for protection from fire due to leakage current. The design engineer sets the sensitivity for each circuit under SS 638 and the project specification. The Himel HDB3VR range is listed in 10, 30, 100 and 300 mA versions.
No. An RCCB only responds to current leaking to earth. Trans-Digi Global’s product page states that RCCBs do not provide complete overload or short-circuit protection on their own. In a starter panel, the RCCB works alongside an MCB, MCCB or motor circuit breaker, which clears overloads and short circuits.
Set it to the full-load current shown on the motor nameplate. Schneider Electric states that the overload dial represents the motor’s nominal current. Do not set it to the breaker or contactor rating. If the relay trips during normal starts, check the trip class and the motor’s run-up time before changing anything.
Send Jason the model or your motor rating — we'll confirm availability the same business day.
WhatsApp UsSend us your motor rating, voltage, application and quantity. We'll get back to you fast.
